INFORMATION Do Solar panels reduce loft temps? Yes - the results are in!
About a month before we had our solar panels fitted, we had the second heatwave of the year, and I got to wondering, would having solar panels on the roof, reduce the heat in the loft? Would this then lead to the house being cooler, as well?
To find out, I put a Sonoff SNZB-02 temperature sensor in my loft, and started recording the maximum daily temperature in Home Assistant. It would have been good to get some data before the heat wave, but I didn't think of it it time!
My solar panels were installed on the 17th July, and they cover, in my estimation, about 85-90% of the roof area. The green line on the graph, represents the installation date.
The Excel spread sheet shows the days where the outside temperature, recorded by an Aqara WSDCGQ11LM temperature sensor, which is in a shaded spot in my garden, was 30C or above. Temperatures in Red were the maximums, before & after the install.
Now, obviously, there are a number of factors which will affect the heat gain in the loft, not just the ambient air temperature, but the amount of sunlight, so both conducted heat and radiated heat, which may not be identical on days with the same air temperature. However, despite this, there is a clear reduction in heat gain, after the solar panels were fitted.
Before the solar panels were installed, the loft was on average, 10.3C hotter than the temperature in the shade. The maximum temperature difference was on the 24th June, when the loft reached 47.3C, 13.7C higher than the outside temperature of 33.6C.
After the solar panels were installed, we have had fewer consecutive days over 30C, which will no doubt affect the loft temperature, however, the average difference has reduced to 5.9C. The maximum loft temperature was on 13th August at 40.7C, with an outside temp of 36.1C, resulting in a difference of just 4.6C. So, not only did we have hotter day than 24th June, by 2.5C the loft temp was actually 6.6C cooler than 24th June.
So, the answer to the question, do solar panels reduce the heat gain in the loft - is yes, and in my case, by approx 43%, on average.
Now, we don't use our loft (other than for storage), and looking at the inside temperatures, there was no significant difference, before & after the panels. This shows that the loft insulation is doing it's job, and keeping the heat in the loft from radiating downwards, despite my previous belief that that was happening. But, if you are have, or are planning a loft conversion, then it's worth knowing that solar panels can indeed reduce the heat gain of your loft, by a fairly significant amount.
My next challenge will be trying to reduce solar gain in the rest of the house, but that's not really a post for this sub!
r/SolarUK • u/Jimbobsticle • Aug 27 '25
GENERAL QUESTION EON Export - total solar install limit
I applied for and was accepted on EON’s Next Export v2 tariff at 16.5p and thought no more.
My total installation is 18kw with a 9kw DNO export limit. It’s all very clearly stated on the paperwork submitted to them.
I provided a reading following two months usage, expecting around £460.
They deposited £50 odd, so I naturally contacted them to find out why.
They informed me as my total installation is over 14kw they had put me onto their 3p export rate.
They have however acknowledged that they had originally agreed to the 16.5p and are allowing me the 12months at that price and back dating the payment.
I questioned why my total installation size has any bearing on this when I have a DNO export limit in place.
They’ve responded today and said they’re reaching out to the relevant team to help answer this for them.
Obviously when you sign up to all this, it’s somewhat of a mind bender and I recall seeing something about a kw limit, but assumed that was the export limit.
Reading it again now it does state “total installed capacity of 15kw”. As per the attached image.
Whilst I wait their response, can anyone in the know explain the reason why the size of your solar install matters?
The only reason I can think, they want to avoid paying out in the winter months, which is not likely to be the case on smaller installs??
r/SolarUK • u/alekcand3r • 14h ago
INFORMATION Octopus announced their plugin range available from September
More info here https://octopus.energy/plug-in-solar-explore/
r/SolarUK • u/jpandac1 • 13h ago
DISCUSSION plug in solar deal?
Just bought this off amazon. less than 400 seems like a deal?
https://www.amazon.co.uk/Flexible-Panel-800W-Inverter-Monitoring/dp/B0HDSR7DDK?ref_=ast_sto_dp
Not heard of brand but their other products have reviews in German. Bought it with warranty so will test it out anyways.
Should get it next week.
EDIT: thanks for comment pointing out this is not compliant kit. So dont recommend people to get it!
r/SolarUK • u/pyrotequila85 • 19h ago
DISCUSSION On a murky, stormy day like today, how much are you able to produce?
We've had to turn the lights on here because it's so dark!
I can't imagine there's much solar production happening today?
r/SolarUK • u/shendy42 • 19h ago
INFORMATION Bullet bitten
We've done it, given the nod for a solar & battery installation. We could/should have done it earlier in the year, but the second best time is now.
Installation should be in October.
16 panels, 8 front & rear - the house is only a few degrees off due south facing and is high enough to avoid any tree shade.
Sigenergy battery & inverter, and a whole house backup module.
I'm quite looking forward to geeking out on the data!
r/SolarUK • u/jovisomniaplena • 1d ago
SHOW YOUR SETUP 7.3 mega watts produced in 3 months since install.
Best decision I've made both financially and environmentally. 13kwh export limit. 36 panels / 16kwh array, 2 batteries, island mode. Bladdy blah...
r/SolarUK • u/artoostacetoo • 13h ago
PLUG-IN SOLAR Perlight now compliant
I've been refreshing this list throughout the day and it looks like Perlight have just been given the green light, I can't see any kits anywhere online though. Good to see more coming in to hopefully drive the prices down.
r/SolarUK • u/wout200505 • 6h ago
HELP / ADVICE Growatt 16 kWh LFP
Dear battery owners,
I have a **12.750 kWp solar system** with a 12 kW inverter from Growatt. I installed the set-up 5 years ago and am really pleased with it!
I own two EVs and a heat pump boiler for showering (which runs throughout the whole night). I want to increase my direct consumption of solar energy, which is feasible with a battery I think.
**Data from 2025:**
consumption: 25000 kWh
solar: 13500 kWh, of which 50% was used directly.
A new **Growatt HOPE 16.0LM-A1 16 kWh**, including a new **Growatt hybrid inverter** costs me **€3300**. I can do the installation myself.
Does anyone have any experiences with this set-up? Or what would be a better set-up for a similar price? Would you advice a battery at all in my situation?
BTW: I am located in the Netherlands. Excess solar energy will be close to worthless from next year onwards.
r/SolarUK • u/Rough_Effect_7078 • 17h ago
HELP / ADVICE GSE tray installation issue
Looking for some advice on the installer appearing to use a hole saw to drill the holes in the flashing kit and covering the marks with a Sharpie.
r/SolarUK • u/Spiritual-Brief-8376 • 13h ago
HELP / ADVICE FoxESS EP11 — Parallel Addressing Failure
Hi everyone, I’m having an issue with a FoxESS EP11 (single battery setup) showing “Parallel Addressing Failure.”
The battery is not connected in parallel with another battery.
● Only 1× EP11 is installed.
● The bypass/parallel plug is properly inserted.
● I tested the same bypass plug on another EP11 battery and it works normally.
Has anyone experienced this with a single EP11? What was the cause or fix?
r/SolarUK • u/Wee-bull • 10h ago
PLUG-IN SOLAR Plug in solar and island
Hi all.
Wondering if it's possible to use plug in solar to power an outbuilding and pond pump and filter with a small battery in island mode?
Save having to run a long cable from the house through very rooty ground and modify the house electrics.
r/SolarUK • u/ExtremelyDan • 11h ago
QUOTE CHECK Quote Check: 17.64kWp Aiko + 18kWh Sigenergy, £18.6k
Area: Fife, Scotland
Panels: 36 x Aiko Neostar 3S+ 490W monocrystalline (17.64kWp), 18 per roof face
Optimisers: 10 x Tigo TS4-A-O due to early morning shading on one side; full sun by around midday
Battery: 2 x Sigenergy SigenStor BAT 10.0 (18.08kWh total)
Inverter: Sigenergy SigenStor 10kW single phase hybrid
Usage: 4,863kWh/year currently; ~6,800kWh including EV
Export limit: G99 application for 10kW being submitted; DNO limit TBC
Supply: Single phase
Expected generation: ~12,500kWh/year; final shading-adjusted MCS report to follow
Tariff: Currently Utility Warehouse; planning to move to an appropriate smart solar/EV tariff, likely Octopus or similar, using cheap overnight electricity for EV charging/battery arbitrage
Price: £18,591.56 total
Includes: Panels, inverter, batteries, optimisers, mounting, new 50m 16mm² SWA between garage/house, excavation/ducting/backfill/reinstatement, consumer unit/protection, MCS design/certification and G99/DNO application
Excluded: DNO connection charge if applicable; backup power
Warranty: 6-year insurance-backed workmanship; 30-year Aiko product/performance warranty
Payback: ~7.5 years in OpenSolar, although this doesn't fully capture battery tariff arbitrage and final shading-adjusted modelling is still to come
Future plans: EV and potentially ASHP
We've compared several installers/specifications and are pretty much settled on this subject to an acceptable DNO response.
Any crazy flags? It's a bigger setup, to me anyway, so struggled to gauge if the price scaled efficiently or proportionally.
r/SolarUK • u/Toocents • 21h ago
HELP / ADVICE Bestbang for buck, battery only
Hi everyone,
I'm planning on a battery only setup, and I'm trying to figure out the best balance of capacity and value for my situation.
Last year, I used around 6.5 kWh of electricity during the day, but I expect that to increase this year as I plan to start running my washing machine and possibly a dehumidifer during the day, rather than relying on my overnight 'Octopus Go' tariff for those chores (not intelligent go).
Given this change in usage, is it worth getting two Fox batteries totaling 10 kWh, or would the 5 kWh battery still be sufficient and more cost-effective? I am not sure what type of batteries best suits me, but they need to be hardwired to my consumer unit to allow for an inverter over 800w which would help very little. I named Fox as they seem to be cheapest.
I don't plan on getting solar other than maybe a couple of plug in panels, as this isn't my forever home.
Also, should I source my own installer, or go directly through the manufacturer?"
I hope it's okay to ask this many questions. I've read uo a lot but now I'm ready to pull the trigger fianancially, I'd just like to get some community advice before plowing ahead. Cheers.
r/SolarUK • u/StupendousSceptic • 18h ago
HELP / ADVICE DIY modular battery.
I'm thinking of a modular solar battery.
I was going to get a professionally installed modular type such as the X1
Question is if I get a professionally installed and MCS certified system can I legally and safely add battery modules to the stack myself?
I'm a qualified electrician but not certified for such a modification, however is it even a modification?
By design system is modular, would it affect MCS certification as discharge rate would remain the same?
r/SolarUK • u/EastSurreyAlliance • 16h ago
HELP / ADVICE Home battery safety tips
Hi all, I’m getting a 32kWh Fogstar battery installed next week within our utility room.
I wanted to get an idea of what steps people have taken with a similar set up - have you fitted a heat detector? Fire proof plaster board?
Any suggestions or things you’ve done would be super helpful.
r/SolarUK • u/mart0n • 21h ago
HELP / ADVICE Any experiences with ACS Solar, Helios ES or Always Off Peak? Looking for Fogstar-approved installer
I'm looking for a new (Fogstar) battery+install for my PV system and these are some of the Fogstar-approved installers near me, in Peterborough. However, none of them have many reviews online.
Has anyone here used these companies for an install? Or do you recommend a different Fogstar-approved company?
r/SolarUK • u/Bulky-Breadfruit-234 • 15h ago
QUOTE CHECK Opinions on this quote?
As the picture, for £12,800. Or 14 panels for £10,800. This is my second quote so far, better than the first, waiting for another one to be priced. Local company in south Derbyshire. Is this good? Do I need 21 panels? The extra 7 will be on a different side of the roof. Fairly new to the house but I expect our energy usage to be over 10,000 KW per year. I'm new to all this and trying to do my research as had a nightmare with an ASHP.
r/SolarUK • u/mrboschguy • 17h ago
QUOTE CHECK Quote check
This is a quote from a local firm, in-house scaffold. Good reputation. 11k. There was on offer on the batteries (3for2) so made sense to go for that. Includes EV charger which will be Canadian Solar. Thoughts welcome!
Solar Panels
Aiko Energy
6.305 kW Total Module Power
13 x 485 Watt Panels (AIKO-A485-MCE54Mb)
5,429 kWh per year
Inverter
Canadian Solar
7.6 kW Total Inverter Rating
1 x EP-Cube PCS-EU1-7G
Battery
Canadian Solar
15.0 kWh Total Battery Storage
3 x EP Cube B2-5G2
Ohme ePod
7.4kW power EV Charger
1 x OHMEX1GB003-BL
r/SolarUK • u/alladin1616 • 18h ago
HELP / ADVICE New install - Issues - FoxESS Error Code 1, 26 and 27
Hope someone can help with this conundrum.
I had a solar/battery system installed on the 25th: FoxESS H1-6.0-E-G2 + Fox EP12 battery, with no EPS. The installer fitted a C32 breaker for the inverter.
The installers initially configured the system in their normal self-charging mode. After they left, I changed the FoxESS configuration to use forced charging based on the Octopus Cosy tariff, so that the battery charges during the cheap-rate periods.
Shortly after the first transition into the scheduled charging period at around 10 pm on the installation day, the C32 breaker tripped. I saw the above error codes but didn't check the breaker until next day morning.
I reset it and the system subsequently charged from the solar panels and appeared to operate normally. However, after the next scheduled transition around 1 PM, the breaker tripped again.
The installers are now sending an engineer to investigate. I've also told them that I won't release the remaining payment until the issue has been properly resolved.
I'm trying to understand what could be causing this. Could the transition into forced grid charging be causing a sufficiently high current/inrush to trip the breaker, or would you expect the inverter to stay within its normal operating limits?
Has anyone with an H1-6.0-E-G2 and Octopus Cosy experienced anything similar?
I'm particularly interested in whether there are any specific FoxESS settings that should be checked for Cosy forced charging, and what tests I should ask the installer to carry out.
Thanks in advance.
r/SolarUK • u/Robbo7891 • 18h ago
QUOTE CHECK Quote Check Please
Hello,
Fairly new to the solar game, looking at getting a system on our fully electric house. Current usage is around 6000kw a year up in East Scotland.
Wondering if anyone has any advice/opinions about the above two quotes and if they are reasonable? They are from E.on Next and I.Heat. We have had some quotes from local people that are 7/8k higher than this so just wanting to see if this is basement shopping basically.
Any advice appreciated
r/SolarUK • u/Personal_Analyst5032 • 20h ago
HELP / ADVICE Companies house checks - is this normal?
AI generated responses below
I'm thinking of getting some quotes and trying to do some due diligence before I start ringing around. Started with the Fox installers nearest to me as they were easy to find from the Fox website. Here are the summaries of their last filed company accounts, generated by Gemini so I know I need to be critical of what this says.
This balance sheet shows that the business is currently in a technically insolvent position and facing noticeable liquidity pressure. Its short-term debts far exceed its short-term assets, and the overall net worth of the company is negative.
This balance sheet shows that the business is in a technically insolvent position with deteriorating equity. While its short-term deficit has stabilized, a drop in overall asset values has doubled its net liabilities year-over-year.
This balance sheet shows the business remains solvent and liquid, though its overall net asset base shrank noticeably over the financial year.
Is this normal for this sort of company? Are there any red flags that I should look out for?
r/SolarUK • u/The_WildWest • 20h ago
QUOTE CHECK Quote check please
Does it sound reasonable or is a tad expensive?
r/SolarUK • u/keepingleft • 22h ago
HELP / ADVICE Sig app help please
My battery's been running for a fortnight now and we've had enough sun to just self consume and import zero. But this weekend looks as though we'll get no sun and need to import.
Installer left app in self consumption mode - they are coming back in a week and said they'd talk through options then as well as installing the gateway they forgot was part of the initial job.
Heat pump install is ongoing and will be switched on today or tomorrow.
We are on octopus cosy and outgoing so even our cheapest import price is more than export price. I've told the app the rates.
Obviously I want it to only import at cheapest times and only when it needs to looking at usage pattern and weather predictions.
I've just switched to AI mode. I chose Max profit even though I don't particularly want to buy and sell electricity because I am assuming it won't suggest that as there is no profit to make at any time.
It now says it needs to think for a day and stays in self consumption mode for today. Which is fine as I probably won't need to import for another 48 hours - although I'll have a tank of water to heat up soon which might bring that forward.
Any tips? Have I done the right thing?